Product Overview
Product Details
Data Download
Related Products
GW1series outdoor MV isolate switch is the high voltage switch equipment of composite structure, is suitable for outdoor 12kV line net with voltage and no load, to make opening and close. With CS□ type manpower operate machinery, can avoid earth line with power and composite flash-locks etc wrongoperate.
The operator is no need to put another earth line. Pollution-proof typeisolate switch satisfy customer in filthy conduction area. It can solve the pollution of shed when it is working.
Conatct Us
1. The altitude above sea level: 2000m
2. The ambient air temperature: -40℃~40℃ wind speed does not exceed 35m/s.
3. The earthquake intensity does not exceed 8 degrees.
4. The working situation is without frequent violent vibration.
5. The installation site of ordinary type isolator s hould be kept away from gas, smoke chemical deposition, salt-spray fog, dust and other explosive and corrosive maters that affect seriously insulation and conduction
capability of the isolator .
6. Pollution i-proof type isolator is applicable to severe filthy conduction area, however, it shouldn’t be any explosive matters and matters causing fire .
Item | Unit | Technical parameters | |||||||
Rated voltage | kV | 10 | 15 | 20 | |||||
Max. operating voltage | kV | 12 | 17.5 | 24 | |||||
Rated insulation level | 1min. power frequency withstand voltage | To earth | kV | 38 | 42 | 50 | |||
Across open DS | kV | 42 | 48 | 60 | |||||
Rated lightning impulse withstand voltage | To earth | kV | 75 | 105 | 125 | ||||
Across open DS | kV | 85 | 120 | 145 | |||||
Rated frequency | Hz | 50 | |||||||
Rated current | A | 200 | 400 | 630 | 1250 | ||||
4s short time withstand current | kA | 6.3 | 12.5 | 20 | 31.5 | ||||
Peak withstand current | kA | 16 | 31.5 | 50 | 80 | ||||
Mechanism supplied for disconnector | CS8-1, CS8-D, CD8-5 Rain type manual mechanism or CX6 motor drive mechanism |
Item | Unit | Technical parameters | |||||||
Rated voltage | kV | 12 | 24 | 33 | |||||
Max. operating voltage | kV | 15 | 27 | 35 | |||||
Rated insulation level | 1min. power frequency withstand voltage | To earth | kV | 40 | 50 | 80 | |||
Across open DS | kV | 47 | 60 | 90 | |||||
Rated lightning impulse withstand voltage | To earth | kV | 105 | 125 | 180 | ||||
Across open DS | kV | 120 | 145 | 210 | |||||
Rated frequency | Hz | 50 | |||||||
Rated current | A | 200 | 400 | 630 | 1250 | ||||
4s short time withstand current | kA | 6.3 | 12.5 | 20 | 31.5 | ||||
Peak withstand current | kA | 16 | 31.5 | 50 | 80 | ||||
Mechanism supplied for disconnector | CS8-1, CS8-D, CD8-5 Rain type manual mechanism or CX6 motor drive mechanism |
Connect pole
1. Φ12Spindle
2. Washer12
3. Open bolt4 25
4. Bend coupling
5. M16Nut
6. Pole
7. 3/4″ Water gas pipe
8. Connect pole head
Product model number | A | B | C |
GW1-12G/400A | 510 | 555 | 18 ×24 =4 |
GW1-12G/630A | 530 | 555 | 18 ×24 =4 |
GW1-24G/400A | 510 | 555 | 18 ×24 =4 |
GW1-24G/630A | 530 | 555 | 18 ×24 =4 |