Product Overview
Product Details
Data Download
Related Products
GW5 outdoor MV isolating switch is used for three-phase AC 50Hz outdoor high voltage electrical equipment, used for the line to switching under voltage pressed no load condition, and electrical isolation the maintenanced high voltage bus, circuit breakers and other electrical equipment and charged high voltage line, can also be used for the opening and closing small capacitance or inductance current. When the knife in the normal break position, can provide a insulation distance consistent with safety requirements. Widely used in 35~110kV substation.
Conatct Us
1. The ambient temperature: upper limit +40℃,lower limit -40 ℃;
2. Altitude: no more than 3000m;
3. Wind speed: not more than 35m/s;
4. Earthquake intensity: do not exceed 8 degree;
5. Pollution level: no more than III;
6. No severe vibration, no corrosive gas, no fire, no explosion danger place.
Item | Parameters | |||||
Unit | GW5- 40.5 | GW5-72.5 | GW5-126 | GW5-145 | ||
Rated voltage | kV | 40.5 | 72.5 | 126 | 145 | |
Rated current | A | 630/1250/1600/2000 | ||||
Rated frequency | Hz | 50 | ||||
Disconnector | Rated peak withstand current | kA | 50/80/100 | |||
Rated short-time withstand current | kA | 20/31.5/40 | ||||
Rated short circuit duration | s | 4 | ||||
I type earth knife |
Rated peak withstand current |
kA | 25 | |||
Rated short-time withstand current | kA | 10 | ||||
Rated short circuit duration |
s | 4 | ||||
II type earth knife |
Rated peak withstand current |
kA | 100 | |||
Rated short-time withstand current | kA | 40 | ||||
Rated short circuit duration |
s | 2 |
1. Connecting terminal
2. Main contact
3. Main contact finger
4. Porcelain insulator
5. Switch base
6. Cross-pin type joint
7. The main knife vertical rod
(1 galvanized steel user owned)
8. Friction plate
9. The main operating mechanism
(CJ6 electric operation or CS17 manual operation)
10. The main knife three-phase linkage rod
The main knife handle at the closing position
The main knife handle is in the off position
Earthing switch operation handle is in the closing position
Earthing switch operation handle is in the off position