JN22-40.5/31.5 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Appliable in the place without corrosive, flammable gas and water place 6. With no frequently intense vibrant place around. Technical data Item Units Data Rated voltage kV 35 Maximum voltage kV 40.5 Rated short time withstand current kA 31.5 Rat...ZW32Y-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude: ≤2000m; 3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃ . Technical data Item Unit Parameter Rated voltage kV 12 Rated insulation level 1min power frequency withstand voltage Dry test Wet test kV 42/ fracture 48 kV 34 ...KYN61-40.5 Metalclad AC Enclosed Switchgear, Wi...
Selection Operating conditions 1. Ambient air temperature: -15℃ ~+40℃ 2. Altitude: ≤1000m 3. Relative humidity : Daily average≤95%; Monthly average≤90% 4. Earthquake intensity:≤magnitude 8. 5. Applicable in the places without corrosive and flammable gas. Note: Customized products are available. Features 1. The cabinet is made of aluminum-zinc coated sheet processed by CNC equipment and assembled with bolts or rivets, with a fully modular structure. 2. This switchgear has various functions to...FZN21/FZRN21-12 Indoor Vacuum Load Switch
Selection Operating conditions 1. Altitude: no more than 1000m; 2. The environment temperature: upper limit +40℃, lower limit -30℃; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Saturated steam pressure: daily average value is not higher than 2.2×10 -3 Mpa, monthly average is not higher than 1.8×10 -3 Mpa; 5. No severe vibration, no corrosive gas, no fire, no explosion danger place. Technical data Item Unit Parameter Techn...ZN63(VS1)-12 Indoor Vacuum Circuit Breaker (Ins...
Selection ZN63 - 12 T 630 - 25 HT P210 Model Rated voltage(KV) Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV T: Spring type 630,1250, 1600,2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63-12 adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the mod...LFS-10Q Current Transformer
Selection Structural introduction This type of current transformer is fully enclosed and post type. It has a good ability of insulation, moisture proof and antipollution. It is small and light. It can be installed at any place and any direction. Technical data 1. Rated insulation level: 12/42/75kV; 2. Rated secondary current: 5A,1A; 3. Refer to the table for rated primary current, accuracy classed combination, rated output, rated dynamic and thermal current. 4. The conditions of partial disc...