Product Overview
Product Details
Data Download
Related Products
The product is used in overload or short-circuit protection for electric transformer. The current limiting means that the fuse will cut off the circuit before the short-circuit current reaches the peak value.
Conatct Us
Current which passes the fuse when being1.3 times of itsspecified electric current,Do not fusing for an hour; Whenthe current
through the fuse is 2 times of its specinedelectric current,fusing in an hour;Refer to its fusingfeature curve in chart 1when select the fuse.
Figure 1 RN1/RN3“An-second” characteristic curve
3 | 6 | 10 | 35 | |||||||||||||||||||||
Rated current (A) | 20 | 100 | 200 | 300 | 400 | 200 | 75 | 100 | 200 | 300 | 20 | 50 | 75 | 100 | 200 | 7.5 | 10 | 20 | 30 | 40 | ||||
Max breaking curent KV effective vakue | 40 | 1.3 | 1.3 | 1.3 | ||||||||||||||||||||
The mininum breaking current Expresswith specified electric current multipe | nuprovide | 1.3 | nuprovide | 1.3 | nuprovide | 1.3 | nuprovide | 1.3 | ||||||||||||||||
Three-phase maximum cut-off capacity(MVA ) | 8 | 8.9 | 10.8 | 15.7 | 15.7 | 8.5 | 9.6 | 13.6 | 13.6 | 17 | 10 | 11.5 | 14.5 | 21 | 21 | 10 | 20 | 27 | 27 | 27 |
The fuse pipe is the main part of fuse, it is made by installing the fuse wire in the porcelain pipe, filing the quartzsand in the porcelain pipe and sealing to-ends of pipe.For the fuse pipe with rated current below 7.5Aand 35V ratedvoltage, its fuse wire is rolled on the special porcelain core, referening to chart 2.a. for the fuse pipe with rated currentabove 7.5A, its fuse wire is hang in the porcelain pipe,referening to the chart.
Chart 2-the section of style fuse pipe
Chart 3-the section of style fuse pipe
1. Cover
2. Cap
3. Porce lain pipe
4. Fuse wire 5.Quartz sand
5.Quartz sand
6. lndicator fuse wire
7. Spring
8. lndicator
9. Porcelain core
10. Rubber washer
Product type | Product code | Diagram number | Rated voltage | Fuse current A | Main size | |||||
number | A | a | L | H1 | H | b | ||||
RN1-6/2 | RN3 | Figure 3 | 6 | 2 | 310 | 500 | 550 | 125 | 235 | 108 |
RN1-6/3 | RN3 | 3 | ||||||||
RN1-6/5 | RN3 | 5 | ||||||||
RN1-6/7.5 | RN3 | 7.5 | ||||||||
RN1-6/10 | RN3 | 10 | ||||||||
RN1-6/15 | RN3 | 15 | ||||||||
RN1-6/20 | RN3 | 20 | ||||||||
RN1-10/2 | RN3 | 10 | 2 | 410 | 600 | 650 | ||||
RN1-10/3 | RN3 | 3 | ||||||||
RN1-10/5 | RN3 | 5 | ||||||||
RN1-10/.7.5 | RN3 | 7.5 | ||||||||
RN1-10/10 | RN3 | 10 | ||||||||
RN1-10/15 | RN3 | 15 | ||||||||
RN1-10/20 | RN3 | 20 | ||||||||
RN1-10/25 | RN3 | 25 | ||||||||
RN1-10/30 | RN3 | 30 |
Product type | Product code | Diagram number | Rated voltage | Fuse current A | Main size | ||||
number | A | a | L | H | b | ||||
RN1-3/150 | RN3 | 3 | 150 | 270 | 400 | 450 | 350 | 108 | |
RN1-3/200 | RN3 | 200 | |||||||
RN1-6/100 | RN3 | Figure 6 | 6 | 100 | 360 | 500 | 550 | ||
RN1-6/150 | RN3 | 150 | |||||||
RN1-6/200 | RN3 | 200 | |||||||
RN1-10/75 | RN3 | 10 | 75 | 460 | 600 | 650 | |||
RN1-10/100 | RN3 | 100 |
Product type | Product code | Diagram number | Rated voltage | Fuse current A | Main size | |||
number | A | a | L | b | ||||
RN1-10/80 | RN3 | Figure 7 | 10 | 80 | 460 | 600 | 650 | 108 |
RN1-10/100 | RN3 | 10 | 100 | |||||
RN1-10/150 | RN3 | 10 | 150 | |||||
RN1-10/200 | RN3 | 10 | 200 |