ZN28-12 indoor MV vacuum circuit breaker is high indoor switch equipment of three-phase AC 50Hz, rated voltage 12kV. The product conforms to the GB1984-89 standard, the product structure has two forms: the switch body and the actuator is mounted together or switch body and actuator installed separately. Integrated structure is ZN28-12 basic model; split structure is ZN28A-12 type, suitable for various kinds of fixed type switch cabinet, such as GG-1A (Z), XGNZ-10 (Z) etc.
It can be equipped with CD17 type DC electromagnetic actuator and CT17, CT19 spring type operating mechanism.
Conatct Us
1. The environment temperature: upper limit +40℃, lower limit -15℃;
2. Altitude: ≤2000m;
3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%;
4. Earthquake intensity: less than 8 degrees;
5. No fire, explosion, pollution, chemical corrosion and severe vibration place.
Item | Unit | Parameter | |||
Parameters of voltage, current, life | |||||
Rated voltage | kV | 12 | |||
Rated short time power frequency withstand voltage (1min) | kV | 42 | |||
Rated lightning impulse withstand voltage (peak) | kV | 75 | |||
Rated frequency | Hz | 50 | |||
Rated current | A | 630 1250 |
630 1250 |
1250 1600 2000 2500 |
1600 2000 2500 3150 |
Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | 40 |
Rated short-time withstand current (RMS) | kA | 20 | 25 | 31.5 | 40 |
Rated peak withstand current | kA | 50 | 63 | 80 | 100 |
Rated short-circuit closing current | kA | 50 | 63 | 80 | 100 |
Rated single / back-to-back capacitor bank breaking current | A | 630/400 | |||
Rated short-circuit current duration | S | 4 | |||
Rated short-circuit current breaking times | Times | 50 | 30 | ||
Rated operating sequence | O-t-CO-180s-CO rated short-circuit breaking current less than 31.5kA, t=0.3s rated short-circuit breaking current 40kA, t=180s |
||||
Rated operation voltage | ≌ 220/110 | ||||
Mechanical life | Times | ≥10000 | |||
Mechanical property parameters | |||||
Open clearance between contacts | mm | 11±1 | |||
Overtravel | mm | 4±1 | |||
Contact closing bounce time | ms | ≤2 | ≤3 | ||
Three-phase, switching synchronism | ms | ≤2 | |||
Average opening speed | m/s | 0.9~1.3 | |||
Average closing speed | m/s | 0.4~0.8 | |||
Opening time (rated voltage) | ms | ≤60 | |||
Closing time (rated voltage) | ms | ≤100 |
Type | H | H1 | H2 | H3 | A | A1 | A2 | B | B1 | B2 | B3 | |||
ZN28-12/T | 2500 3150 |
-40 | 780 | 700 | 268 | 371 | 581 | 450 | 390 | 700 | 560 | 275 | 690 | |
ZN28-12/T2000-31.5 | 697 | 677 | 235 | 347 | 550 | 380 | 330 | 634 | 480 | 250 | 620 | |||
ZN28-12/T | 630 1250 |
- | 20 31.5 |
697 | 677 | 235 | 347 | 550 | 380 | 330 | 594 | 440 | 230 | 580 |
Rated current | 20KA, 25KA, 31.5KA | 40kA | ||
Code | A | B | A | B |
Data | 250 | 610 | 275 | 690 |