ZN63C-12 series indoor AC MV vacuum circuit breaker (hereinafter referred to as circuit breaker) is an indoor switchgear with three-phase AC 50Hz and rated voltage of 12kV, which can be used for the control and protection of electrical facilities in industrial and mining enterprises, power plants and substations It is suitable for places with frequent operations.
The circuit breaker adopts an integrated design of the operating mechanism and the circuit breaker body, and is used as a fixed installation unit.
Standard: IEC 62271-100
Conatct Us
ZN63 | C | - | 12 | P | / | T | 630 | - | 25 | FT | R | P210 |
Name | Structure | - | Rated voltage(KV) | Pole type | / | Operating mechanism | Rated current(A) | - | Rated short-circuit breaking current(KA) |
Installation | Main circuit wiring direction |
Phase distance |
Indoor vacuum circuit breaker | Side operation |
- | 12:12KV | No mark: Insulating cylinder type P: Solid-sealing type |
/ | T:Spring type | 630 1250 1600 2000 2500 3150 4000 |
- | 20 25 31.5 40 |
FT: Fixed type | L: Left R: Right |
P210 |
Note:
1. order a ZN63 side-mounted main circuit with right wiring, rated voltage 12KV, rated current 630A, rated short-circuit breaking current 25KA.
1. The ambient temperature is not higher than +40°C and not lower than -15°C (storage and transportation at -30°C are allowed);
2. The altitude is not higher than 1000m;
3. Relative temperature: the daily average is not more than 95%, and the monthly average The value is not more than 90%, the daily average value of saturated vapor pressure is not more than 2.2×10-’MPa, and the monthly average value is not more than 1.8×10MPa;
4. The seismic intensity does not exceed 8 degrees;
5. There is no fire, explosion hazard, serious pollution, Places subject to chemical corrosion and severe vibration.
1. The arc extinguishing chamber and operating mechanism of the circuit breaker are arranged in a front-to-back configuration and connected as a whole through a transmission mechanism.
2. Depending on the design of the switchgear, the primary conductive output can be divided into right output and left output.
3. The main conductive circuit is primarily designed with an insulating cylinder, but it can also be designed with a fixed-sealing pole method.
4. The operating mechanism adopts a spring energy storage type and has both electric and manual energy storage functions.
5. It features an advanced and rational buffering device, ensuring no rebound during circuit interruption and reducing the impact and vibration during circuit breaking.
6. It requires minimal or no adjustments and requires very little maintenance or is maintenance-free.
7. The mechanical lifespan can reach 20,000 cycles.
Technical datas are shown in Table 1
Item | Unit | Value | ||
Rated voltage | 12 | |||
Rated insulation level |
Rated lightning impulse withstand voltage (peak) 1min power frequency withstand voltage |
KV | 78(Phase-to-phase),80(Phase-to-phase) 42(Phase-to-phase),48(Phase-to-phase) |
|
Rated short-circuit breaking current(KA) | KA | 25 | 31.5 | |
Rated current | A | 6,301,250 | 63,012,501,600 | |
Rated thermal stable current (effective value) | KV | 25 | 31.5 | |
Rated dynamicstable current (peak value) | 63 | 80 | ||
Rated short-circuit making current (peak value) | 63 | 80 | ||
Rated short-circuit breaking current breaking times | Times | 50 | ||
Secondary circuit power frequency withstand current | V/min | 2000 | ||
Rated operating sequence | “Opening -0.3s – closing and openin g -180s – closing and opening “ | |||
Rated thermal stability time | S | 4 | ||
Rated single/back to back capacitor bank breaking current | A | 630/400 | ||
Mechanical life | 20000 |
The mechanical characteristic parameters are shown in Table 2
Item | Unit | Value |
Contact distance | mm | 11±1,9±1(Solid sealing type) |
Contact travel | 3.5±1 | |
Average closing speed (6mm~contact closed) | m/s | 0.4~0.8 |
Average opening speed (contact separation -6mm) | 0.9~1.3 | |
Opening time (rated voltage) | ms | 20~50 |
Closing time (rated voltage) | 35~70 | |
Contact closing bounce time | ms | ≤2 |
Three phase opening asynchrony | ≤2 | |
Allowable cumulative thickness of wear for moving and stationary contacts | mm | 3 |
ain electrical circuit resistance | μ Ω | ≤(630A),≤ 45( 1250A) |
Contact pressure of closing contacts | N | 2400±200( KA),3100±200( 31.5KA) |
Opening and closing coil parameters are shown in Table 3
Item | Closing coil | Opening coil | Value |
Rated operating voltage | AC110/220 DC110/220 |
AC110/220 DC110/220 |
The opening coilshall not open when it is less than 30% of the rated operating voltage |
Coil power | 264 | 264 | |
Normal operating voltage range | 85% -110% rated voltage | 65% -120% rated voltage |
Energy storage motor parameters are shown in Table 4
Model | Rated voltage ( V ) |
Rated input power ( W ) |
Normal operating voltage ( V ) |
Energy storage time at rated voltage ( S ) |
ZYJ55-1 | DC110 CD220 | 50~75 | 85% -110% rated voltage | ≤15 |
Fixed outline size drawing (insulation cylinder
Solid seal type outline dimension drawing (insulation cylinder)