Product Overview
Product Details
Data Download
Related Products
ZN63(VS1)-24 series indoor AC MV vacuum circuit breaker is an indoor switchgear for three-phase AC 50Hz, rated voltage 4KV power system. The market combines years of professional production experience to develop and design a new generation of vacuum circuit breakers.
Standard: IEC 62271-100
Conatct Us
ZN63 | - | 24 | P | / | T | 630 | - | 25 | HT | P210 |
Name | - | Rated voltage(KV) | Pole type | / | Operating mechanism | Rated current(A) breaking current(KA) |
- | Rated short-circuit | Installation | Main circuit wiring direction |
Indoor vacuum circuit breaker | - | 24:24KV | No mark: Insulating cylinder type P: Solid-sealing type |
/ | T: Spring type |
630 1250 1600 2000 2500 3150 4000 |
- | 20 25 31.5 40 |
HT:Handcart type FT:Fixed type | P210 P275 |
Note:
Zn63 (S) adopts a double spring integral mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the model backup;
1. Altitude: 1000m and below;
2. Environmental temperature: upper limit+40 ℃, lower limit -25 ℃;
3. Relative humidity: daily average relative humidity not exceeding 95%, monthly average relative humidity not exceeding 90%, saturated vapor pressure: daily average not exceeding 2.2 × 10 MPa, monthly average not greater than 1.8 × 10 Mpa.
4. Seismic intensity not exceeding 8 degrees;
5. A place free from flammable, explosive, or chemically corrosive substances and intense vibrations.
1. The adoption of a new generation modular spring operating mechanism, which features a compact, simple, well-designed structure, reliable transmission, and easy installation.
2. Integration of the operating mechanism and circuit breaker body: it can be used as a fixed installation unit or combined with a dedicated propulsion mechanism to form a handcart unit.
3. The main power circuit primarily utilizes a solid-sealed pole, and an insulation simplification method can also be selected.
4. The main circuit incorporates a solid insulation structure with an integrated solid-sealed pole, achieving maintenance-free, high reliability, and compact size.
5. The circuit breaker is an E2 grade breaker.
6. The cabinet is equipped with comprehensive five-protection interlocking functions.
Technical datas are shown in Table 1
Item | Unit | Value | ||||
Rated voltage | kv | 24 | ||||
Rated frequency | Hz | 50 | ||||
Rated current | A | 630 1250 |
1250 1600 2000 2500 3150 |
|||
Rated insulation level |
1min p.f Wuthstand voltage |
between pole to earth | kv | 65 | ||
Separation point | 79 | |||||
Rated lightning impulse resistance voltage |
between pole to earth | 125 | ||||
Separation point | 145 | |||||
4s rated short time withstand current | kA | 20 | 25 | 31.5 | ||
Rated short circuit breaking current | 20 | 25 | 31.5 | |||
Rated peak thstand current | 50 | 63 | 80 | |||
Rated short circuit maing curren | 50 | 63 | 80 | |||
Rated short-circuit duration | S | 4 | ||||
Rated breaking current at the fsult of different pbasesearthed | kA | 17.4 | 21.7 | 27.4 | ||
Rated operation sequence | O-0.3s-CO-18os-CO | |||||
Rated operation voltage | V | DC(AC)220/110 | ||||
Electrical endurannce | E2 (grade)* | |||||
Endurannce endurannce | Time | 20000 |
Note:
1. When the rated current is 3150A, forced air cooling is required
2. The GB1984-2003 electrical life B2 standard is implemented, and the number of short-circuit current interruptions is 274 times.
The mechanical characteristic parameters of the circuit breaker are shown in Table 2
Item | Unit | Value | ||||||
Opening distance of contact | mm | 13±1 | ||||||
Over-travel distance of contact | 4±1 | |||||||
Cental distance between poles | 210,275 | |||||||
Permaissibleabrasiom thickness of the comtact | 3 | |||||||
Average opening speed (6nm just opening) | m/s | 1.3±0.3 | ||||||
Average closing speed | 0.6±0.2 | |||||||
Jumping time after contact closed. | ms | ≤2 | ||||||
Asynchrony of throo phase closing, opening | ≤2 | |||||||
Main circuit resistance | Rated current | A | 630 | 1250 | 1600 | 2000 | 2500 | 3150 |
Fixed type breaker | μΩ | ≤50 | ≤45 | ≤35 | ≤35 | ≤30 | ≤25 | |
Truck type breaker | ≤55 | ≤50 | ≤50 | ≤40 | ≤35 | ≤30 | ||
Opening time | ms | ≤50 | ||||||
Closing time | ≤75 | |||||||
Operating performances ofoperating mechanise | 85%~110%(rated voltage) | Reliably close | ||||||
85%~110%(rated voltage) | Reliably open | |||||||
≤30%(rated voltage) | Not open |
Main technical data of operating mechanism as sheet 3
Item | Unit | Value |
Rated opcrating voltage for opening | V | AC/DC220V、AC/DC11oV |
Rated operating voltage for closing | AC/DC220V、AC/DC110V | |
Rated instantaneous over-current tripping curent | A | 5/3.5 |
Rated voltage for charging mnotor | V | AC/DC220V、AC/DC11oV |
Rated output power of charging motor | W | 70 |
Charging time | S | ≤10 |
1min p.f withstland voltage on secondary circnit | V | 2000 |
ZN63(VS1)-24 hand car phase distance 210 outline dimensions (small solid sealed pole type)
Rated current (A) | Rated short-circuit breaking current (kA) | Equipped static contact size (mm) |
630 | 25 | Φ35 |
1250 | 25 | Φ49 |
ZN63(VS1)-24 hand car phase distance 275 outline dimensions (small solid sealed pole type)
Rated current (A) | Rated short-circuit breaking current (kA) | Equipped static contact size (mm) |
630 | 25 | Φ35 |
1250 | 25 | Φ49 |
1600 | 31.5 | Φ45 |
ZN63(VS1)-24 hand car phase distance 275 outline dimensions (big solid sealed pole type)
Rated current (A) | Rated short-circuit breaking current (kA) | Equipped static contact size (mm) |
1600-2000 | 31.5 | Φ79 |
2500-3150 | 31.5 | Φ109 |