• Product Overview

  • Product Details

  • Data Download

  • Related Products

ZN63(VS1)-24 Indoor Vacuum Circuit Breaker

Picture
Video
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker Featured Image
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker Featured Image
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker Featured Image
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker Featured Image
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker Featured Image
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker Featured Image
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker
  • ZN63(VS1)-24 Indoor Vacuum Circuit Breaker
S9-M Oil-immersed  Transformer

ZN63(VS1)-24 Indoor Vacuum Circuit Breaker

ZN63(VS1)-24 series indoor AC MV vacuum circuit breaker is an indoor switchgear for three-phase AC 50Hz, rated voltage 4KV power system. The market combines years of professional production experience to develop and design a new generation of vacuum circuit breakers.
Standard: IEC 62271-100

Conatct Us

Product Details

Selection

ZN63 - 24 P / T 630 - 25 HT P210
Name - Rated    voltage(KV) Pole type / Operating  mechanism Rated current(A)
breaking current(KA)
- Rated short-circuit Installation Main circuit
wiring direction
Indoor   vacuum circuit    breaker - 24:24KV No mark:
Insulating
cylinder
type
P: Solid-sealing
type
/ T:
Spring type
630
1250
1600
2000
2500
3150
4000
- 20
25
31.5
40
HT:Handcart type FT:Fixed type P210 P275

Note:
Zn63 (S) adopts a double spring integral mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the model backup;

Operating conditions

1. Altitude: 1000m and below;
2. Environmental temperature: upper limit+40 ℃, lower limit -25 ℃;
3. Relative humidity: daily average relative humidity not exceeding 95%, monthly average relative humidity not exceeding 90%, saturated vapor pressure: daily average not exceeding 2.2 × 10 MPa, monthly average not greater than 1.8 × 10 Mpa.
4. Seismic intensity not exceeding 8 degrees;
5. A place free from flammable, explosive, or chemically corrosive substances and intense vibrations.

Features

1. The adoption of a new generation modular spring operating mechanism, which features a compact, simple, well-designed structure, reliable transmission, and easy installation.
2. Integration of the operating mechanism and circuit breaker body: it can be used as a fixed installation unit or combined with a dedicated propulsion mechanism to form a handcart unit.
3. The main power circuit primarily utilizes a solid-sealed pole, and an insulation simplification method can also be selected.
4. The main circuit incorporates a solid insulation structure with an integrated solid-sealed pole, achieving maintenance-free, high reliability, and compact size.
5. The circuit breaker is an E2 grade breaker.
6. The cabinet is equipped with comprehensive five-protection interlocking functions.

Technical data

Technical datas are shown in Table 1

Item Unit Value
Rated voltage kv 24
Rated frequency Hz 50
Rated current A 630
1250
1250  1600
2000  2500
3150
Rated
insulation level
1min p.f
Wuthstand voltage
between pole to earth kv 65
Separation point 79
Rated lightning
impulse resistance voltage
between pole to earth 125
Separation point 145
4s rated short time withstand current kA 20 25 31.5
Rated short circuit breaking current 20 25 31.5
Rated peak thstand current 50 63 80
Rated short circuit maing curren 50 63 80
Rated short-circuit duration S 4
Rated breaking current at the fsult of different pbasesearthed kA 17.4 21.7 27.4
Rated operation sequence O-0.3s-CO-18os-CO
Rated operation voltage V DC(AC)220/110
Electrical endurannce E2 (grade)*
Endurannce endurannce Time 20000

Note:
1. When the rated current is 3150A, forced air cooling is required
2. The GB1984-2003 electrical life B2 standard is implemented, and the number of short-circuit current interruptions is 274 times.

The mechanical characteristic parameters of the circuit breaker are shown in Table 2

Item Unit Value
Opening distance of contact mm 13±1
Over-travel distance of contact 4±1
Cental distance between poles 210,275
Permaissibleabrasiom thickness of the comtact 3
Average opening speed (6nm just opening) m/s 1.3±0.3
Average closing speed 0.6±0.2
Jumping time after contact closed. ms ≤2
Asynchrony of throo phase closing, opening ≤2
Main circuit resistance Rated current A 630 1250 1600 2000 2500 3150
Fixed type breaker μΩ ≤50 ≤45 ≤35 ≤35 ≤30 ≤25
Truck type breaker ≤55 ≤50 ≤50 ≤40 ≤35 ≤30
Opening time ms ≤50
Closing time ≤75
Operating performances ofoperating mechanise 85%~110%(rated voltage) Reliably close
85%~110%(rated voltage) Reliably open
≤30%(rated voltage) Not open

Main technical data of operating mechanism as sheet 3

Item Unit Value
Rated opcrating voltage for opening V AC/DC220V、AC/DC11oV
Rated operating voltage for closing AC/DC220V、AC/DC110V
Rated instantaneous over-current tripping curent A 5/3.5
Rated voltage for charging mnotor V AC/DC220V、AC/DC11oV
Rated output power of charging motor W 70
Charging time S ≤10
1min p.f withstland voltage on secondary circnit V 2000

Overall and mounting dimensions(mm)

ZN63(VS1)-24 hand car phase distance 210 outline dimensions (small solid sealed pole type)

product description01

Rated current (A) Rated short-circuit breaking current (kA) Equipped static contact size (mm)
630 25 Φ35
1250 25 Φ49

ZN63(VS1)-24 hand car phase distance 275 outline dimensions (small solid sealed pole type)

product description02

Rated current (A) Rated short-circuit breaking current (kA) Equipped static contact size (mm)
630 25 Φ35
1250 25 Φ49
1600 31.5 Φ45

ZN63(VS1)-24 hand car phase distance 275 outline dimensions (big solid sealed pole type)

product description03

Rated current (A) Rated short-circuit breaking current (kA) Equipped static contact size (mm)
1600-2000 31.5 Φ79
2500-3150 31.5 Φ109