Product Overview
Product Details
Data Download
Related Products
ZW7-40.5 outdoor medium-voltage vacuum circuit breaker is a three-phase AC 50Hz outdoor high-voltage electrical equipment; it is suitable for the control and protection of 20-40.5kV power transmission and distribution systems; it can also be used in the occasions of section circuit breakers and switched capacitor banks; this product can be used with piecewise controller, the reclosing device can realize intelligent sectioning and reclosing control of the power system. A current transformer can be added for measurement and protection. The ring circuit breaker is equipped with a spring or electromagnetic actuator, with reliable mechanical performance and frequent operation; there is no risk of fire and explosion.
The main characteristics of the circuit breaker are excellent breaking performance, vacuum arc, high breaking capacity, mechanical life up to 10000 times, simple structure, maintenance free, and long maintenance cycle; Good insulation performance and strong anti pollution ability; Current transformers can be installed according to customer requirements, with a measurement accuracy of up to 0.2 level, enabling three-phase interaction.
Standard: IEC 62271-100
Conatct Us
1. Ambient temperature: upper limit +40℃, lower limit -30℃; Days difference does not exceed 32K;
2. Altitude: 1000m and the following areas;
3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s);
4. Air pollution level: IV class
5. Earthquake intensity: do not exceed 8 degree;
6. Ice thickness: no more than 10mm.
Item | Unit | Parameter |
Voltage, current parameters | ||
Rated voltage | kV | 40.5 |
Rated short time power frequency withstand voltage (1min) | kV | 95 |
Rated lightning impulse withstand voltage (peak) | kV | 185 |
Rated current | A | 1250, 1600, 2000 |
Rated short-circuit breaking current | kA | 25, 31.5 |
Rated operating sequence | O-0.3s-CO-180s-CO | |
Rated short-circuit current breaking times | Times | 12 |
Rated short-circuit closing current (peak) | kA | 63, 80 |
Rated peak withstand current | kA | 63, 80 |
Rated short-time withstand current | kA | 25, 31.5 |
Rated short-circuit current duration | S | 4 |
Average opening velocity | ms | 1.5±0.2 |
Average closing speed | ms | 0.7±0.2 |
Contact closing bounce time | ms | ≤5 |
Three-phase close (open) synchronization error | ms | ≤2 |
Closing time | ms | ≤150 |
Opening time | ms | ≤60 |
Mechanical life | Times | 10000 |
Rated operational voltage and auxiliary circuits rated voltage | V | DC220, AC220 |
DC resistance of circle every phase (not including transformer) | μΩ | ≤100 |
Dynamic, static contact allowed to wear thickness | mm | 3 |
Weight | kg | 800 |
The ZW7-40.5 shape and size of installation
Installation base diagram